1.Ambient air temperature:maximum+40℃,minimum-15℃
2.Humidity conditions:
3.Seismic intensity:no more than Grade 8.
4.Ambient air shall be free from obvious contamination by corrosive or flammable gases,water vapor,etc.
5.The installation site shall be free from frequent severe vibration.
6.If the equipment is operated under conditions exceeding the normal requirements specified in GB 3906,mutual agreement shall be reached between the user and the manufacturer.
1.Main circuit scheme number,application purpose,single-line diagram,arrangement drawing,floor plan of the distribution room,etc.
2.Schematic wiring diagram of auxiliary circuits and terminal arrangement drawing.
3.Model,specification and quantity of electrical components installed in the switchgear.
4.Requirements for control,measurement and protection functions of the switchgear,as well as requirements for other interlocking devices and automatic devices.
5.If a busbar bridge connection is required between switchgears or for the incoming cabinet,specific data including rated current-carrying capacity,span and height above ground level of the busbar bridge shall be provided.
6.Type and quantity of required accessories and spare parts.
7.Special environmental conditions for switchgear operation shall be fully specified when placing an order.
| Project | Unit | Data | ||
| Rated Voltage | KV | 3.6、7.2、12 | ||
| Rated Frequency | HZ | 50 | ||
| Rated current of circuit breaker | A | 630、1250、1600、2000、22500、3150、4000 | ||
| Rated current of switchgear | A | 630、1250、1600、2000、22500、3150、4000 | ||
| Rated short-time withstand current (4S) | KA | 16、20、25、31.5、40、50 | ||
| Rated peak withstand current (peak) | KA | 40、50、63、80、100、125 | ||
| Rated short-circuit breaking current | KA | 16、 20、25、31.5、 40、 50 | ||
| Rated short-circuit closing current (peak) | KA | 40、50、63、80、100、125 | ||
| Rated insulation level | 1-minute power frequency withstand voltage | Pole to pole, pole to ground | KV | 24、32、42 |
| Between fracture surfaces | KV | 24、32、48 | ||
| Lightning impulse withstand voltage (peak value) | Pole to pole, pole to ground | KV | 40、60、75 | |
| Between fracture surfaces | KV | 46、70、85 | ||
| Protection level | The enclosure is IP4X between compartments, and when the circuit breaker room door is opened, it is IP2X. | |||
Note:
1.The short-circuit capacity of current transformers should be considered separately.
2.The technical parameters of ZN63A-12 are detailed in the corresponding sample.
3.1000m altitude type rated current≤1250A rated breaking current≤31.5KA

Schematic diagram of switchgear structure